Sample Specification
This is a sample specification. The actual project specifications must take into account specific requirements for the project and local construction practices. All the information contained in this sample specification is offered as guidance for proper construction of masonry assemblies and is intended to comply with appropriate industry standards and practices. Final selection or use of any or all of this information is the sole responsibility of the Owner and/or his/her agents.
SECTION 04222 QUIK-BRIK
PART 1 - GENERAL
1.01. SUMMARY
A. Section
Includes:
1. Custom concrete masonry units (CMU),
Quik-Brik.
2. Reinforcement, anchorages, and accessories
3. Masonry fill insulation
B. Work Installed But Not Furnished Under This Section:
1. Support plates and angles with anchor
studs.
2. Sleeve anchors.
3. Expansion bolts.
4. Adhesive anchors.
5. Anchor bolts which are embedded in masonry
for supporting structural members.
C. Related Sections:
1. Section 04060 - Masonry Mortar.
2. Section 04070 - Masonry Grout.
3. Section 04220 - Concrete Masonry Units.
4. Section 05120 - Structural Steel: Support
plates and angles with anchor studs, expansion bolts,
sleeve anchors, adhesive anchors, and anchor bolts
embedded in masonry for supporting structural
members.
5. Section 05500 - Metal Fabrications: Loose
steel lintels and other metal components embedded in
masonry.
6. Section 07900 - Joint Sealer: Rod and
sealant at control joints.
1.02. REFERENCES
A. American Concrete Institute (ACI):
1. ACI 117-90 - Standard Specifications for Tolerances for Concrete
Construction and Materials.
2. ACI 530-99 - Building Code Requirements
for Masonry Structures.
3. ACI 530.1-99 - Specification for Masonry
Structures.
B. American Society for Testing and Materials (ASTM):
1. ASTM A 82 -
Specification for Steel Wire, Plain, for Concrete Reinforcement.
2. ASTM A 153 -
Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware.
3. ASTM A 307 - Specification for Carbon
Steel Bolts and Studs, 60 000 psi Tensile Strength.
4. ASTM A 615 - Specification for Deformed
and Plain Billet-Steel Bars for Concrete Reinforcement.
5. ASTM A 951 -
Specification for Masonry Joint Reinforcement.
6. ASTM C 90 - Specification for Loadbearing
Concrete Masonry Units.
7. ASTM C 129 - Specification for
Non-Load-Bearing Concrete Masonry Units.
8. ASTM C 140 - Methods of Sampling and
Testing Concrete Masonry Units.
9. ASTM C 516 - Specification for Vermiculite
Loose Fill Thermal Insulation.
10. ASTM C 549 - Specification for Perlite Loose
Fill Insulation.
11. ASTM C
920 - Specification for Elastomeric Joint Sealants.
12. ASTM D 994 - Specification for Preformed
Expansion Joint Filler for Concrete (Bituminous).
13. ASTM D 1056 - Specification for Flexible
Cellular Materials - Sponge or Expanded Rubber.
14. ASTM D 2000 - Classification System for
Rubber Products in Automotive Applications.
15. ASTM D 2287 - Specification for Nonrigid
Vinyl Chloride Polymer and Copolymer Molding and
Extrusion Compounds.
C. Masonry Industry Council (MIC): Hot and Cold Weather
Masonry Construction.
1.03. SUBMITTALS
A. Section 01330 -Submittal Requirements: Procedures for
submittals.
1.04. QUALITY ASSURANCE
A. Construction: Construct masonry in accordance with
requirements of ACI 530 and 530.1.
B. Special Inspection and Testing: Provide inspection and
testing in accordance with the Building Code and as
noted on Drawings and will be performed under provisions of
Section 01450.
C. Mock-up: Construct a masonry wall panel to represent the
exterior masonry wall.
1. Construct wall at least 4 feet long by 4
feet high.
2. Locate where directed by Architect/Owner's
Representative.
3. Include reinforcing and minimum of one
control joint and one outside corner.
4. Include joint profile and mortar color.
5. Erect entire mock-up with methods
representative of daily construction and in-progress cleaning practices.
6. Clean one-half of mock-up to represent
final clean down using methods and materials in accordance with
the cleaning requirements herein and leave remainder without
final cleaning for comparison purposes.
7. Receive acceptance of mock-up by
Architect/Owner's Representative before proceeding with masonry
installation.
8. When accepted, mock-up will be used as
standard of quality for masonry Work.
9. Leave field sample in place until project
completion.
10. Mock-up may not remain as part of the Work.
11. Provide on-site inspection by Oldcastle
Architectural Products Group (APG) representative of mock-up
construction and cleaning and submit manufacturer's letter
of approval of the work procedures and
the completed mock-up.
1.05. DELIVERY STORAGE AND HANDLING
A. Damaged Components:
1. Do not use damaged masonry units
2. Do not use damaged components of structure
3. Do not use damaged packaged materials.
4. Do not use masonry units that are
contaminated.
B. Storage:
1. Store different aggregates separately.
2. Protect reinforcement, ties, and metal
accessories from permanent distortions.
3. Store reinforcement, ties, and metal
accessories off the ground.
C. Cleaning Reinforcement: Before being placed, remove
loose rust, ice, and other deleterious coatings from
reinforcement.
1.06. PROJECT CONDITIONS
A. Environmental Requirements (Cold Weather): Follow the requirements of the MIC Hot and
Cold Weather
Construction. Include
the following construction requirements for cold weather procedures:
1. When ambient air temperatures are above
40oF cover tops of walls and masonry elements with plastic or
canvas at end of workday to prevent water from
entering masonry.
2. When ambient air temperatures are below
40oF and above 32oF or temperature of masonry units is below
40oF:
a. Remove visible ice on masonry units before
units are placed in the wall.
b. Do not lay masonry units having a
temperature below 20oF.
c. Heat sand and mixing water to produce
mortar temperatures between 40oF and 120oF at the
time of mixing.
d. Maintain mortar and grout temperatures
above freezing until used in masonry.
e. Cover tops of walls and masonry
elements with weather resistive membrane at end of workday
to prevent water from entering masonry.
3. When ambient air temperatures are below
32oF and above 25oF or temperature of masonry units is
below 40oF:
a. Remove visible ice on masonry units
before units are placed in the wall.
b. Do not lay masonry units having a
temperature below 20oF.
c. Heat sand and mixing water to produce
mortar temperatures between 40oF and 120oF at the
time of mixing.
d. Maintain mortar and grout temperatures
above freezing until used in masonry.
e. Completely cover walls and masonry
elements with weather resistive membrane at end of work
day and keep covers in place for 24 hours.
4. When ambient air temperature is
below 25oF and above 20oF:
a. Remove visible ice on masonry units
before units are placed in the wall.
b. Do not lay masonry units having a
temperature below 20oF.
c. Heat sand and mixing water to produce
mortar temperatures between 40oF and 120oF at the time of mixing.
d. Maintain mortar and grout
temperatures above freezing until used in masonry.
e. Use heat source on both sides of
masonry under construction.
f. Install wind breaks when wind
velocity is in excess of 15 mph.
g. Completely cover walls and masonry
elements with insulated blankets or equivalent protection
at end of workday and keep covers in place for
24 hours.
5. When ambient temperature is below
20oF:
a. Remove visible ice on masonry units
before units are placed in the wall.
b. Do not lay masonry units having a
temperature below 20oF.
c. Heat sand and mixing water to produce
mortar temperatures between 40oF and 120oF at the
time of mixing.
d. Maintain mortar and grout temperatures
above freezing until used in masonry.
e. Provide an enclosure for the masonry
under construction.
f. Use heat sources to maintain
temperatures above 32oF within the enclosure.
g. Maintain masonry temperature above
32oF for 24 hours after construction by enclosure with
supplementary heat, electric heating blankets, infrared
heat lamps, or other acceptable
methods.
B. Environmental Requirements (Hot
Weather): Follow the requirements of the
MIC Hot and Cold Weather Construction. Include the following construction requirements for hot weather
procedures:
1. When ambient temperature is above 115oF or
ambient air temperature is above 105oF and wind velocity
exceeds 8 mph:
a. Shade materials and mixing equipment
from direct sunlight.
b. Maintain sand piles in damp loose
condition.
c. Provide necessary conditions and
equipment to produce mortar and grout having temperatures
below 120oF.
d. Use cool mixing water for mortar and
grout.
e. Maintain temperatures of mortar and
grout below 120oF.
f. Flush mixer, mortar and grout
transport container, and mortarboards with cool water before the
come in contact with mortar or grout.
g. Maintain mortar consistency by
re-tempering with cool water.
h. Use mortar within 2 hours of initial
mixing.
i. Fog spray all newly constructed
masonry until damp, at least three times a day until the masonry
is 3-days old.
2. When ambient temperature is above 100oF or
ambient air temperature is above 90oF and wind velocity
exceeds 8 mph:
a. Maintain sand piles in damp loose
condition.
b. Provide necessary conditions and
equipment to produce and maintain mortar and grout having
temperatures below 120oF.
c. Maintain mortar and grout temperatures
below 120oF.
d. Flush mixer, mortar and grout
transport container, and mortarboards with cool water before the
come in contact with mortar or grout.
e. Maintain mortar consistency by
re-tempering with cool water.
f. Use mortar within 2 hours of initial
mixing.
g. Fog spray all newly constructed
masonry until damp, at least three times a day until the
masonry is three days old.
PART 2 - PRODUCTS
2.01. QUIK-BRIK (CONCRETE MASONRY UNITS)
A. Integrally Pigmented Loadbearing Units: ASTM C 90.
1. Stretcher unit dimensions:
a. Nominal 4 inch high.
b. Nominal 16 inch long.
2. Normal weight
3. Integral metallic oxide pigments.
4. Integral polymer water repellent.
a. Manufacturers:
i. Dry-Block by W.R. Grace and Company (800)
588-7066.
ii. Substitution approval per the manufacturing location only.
5. Manufacturers and Suppliers:
a. Quik-Brik by an Oldcastle
Architectural Products Company. Contact
the Oldcastle National
Accounts office at
877-506-2745.
b. Manufacturers
i. 4D, 800-227-6512.
ii. Adams Products Company, 800-672-3131.
iii. Arthur Whitcomb, 603-298-5959.
iv. Amcor Masonry Products, 800-800-4004.
v. Anchor
Concete Products, 877-592-7425.
vi. Bend Industries, 800-686-2363.
vii. Betco
Supreme, 800-486-4011.
viii. DomineBuilders Supply, 800-836-2565.
ix. Foster Southeastern, 800-462-2225.
x. Jewell Concrete Products, 800-792-3216.
xi. Miller Material Company, 800-289-2244.
xii. Northfield Block, 847-816-9000.
xiii. Schuster's
Building Products, Inc., 800-424-0190.
xiv. Superlite Block, 800-366-7877.
xv. Georgia Masonry Supply,
770-963-5888.
xvi. Oldcastle Coastal, 888-682-7622
c. Distributors
i. Central
Pre-Mix, contact Brent Hostetler 800-950-6290.
d. Colors:
i. Promenade
Blend
ii. Lawson Blend
iii. Earthtone Blend
iv. Sandlewood
Blend
v. Cedarwood Blend
vi. Marous
Blend
vii. Richfield Blend
viii. Autumn Blend
ix. Heritage
Blend
x. Monico Blend
xi. Simon Blend
xii. Wilkesboro
Blend
xiii. Custom Color _________________.
6. Substitutions: Not permitted.
B. Unit Design: Modular two core units sized as indicated
and scheduled. Provide special units for
bond beams,
control and expansion joints, and lintels.
1. Provide units as required for indicated
construction including sill units and solid cap units.
2. Provide units with exposed faces, which
are uniform in appearance.
2.02 REINFORCEMENT AND
ANCHORAGES
A. Horizontal Joint Reinforcement: ASTM A 951.
1. Minimum wire size W1.7 (9 gage) and
maximum wire size W2.8 (3/16 inch wire).
2. Width 1-1/2 to 2 inches less than wall
thickness.
3. Hot-dipped galvanized 1.5 oz. ASTM A 153, Class B2.
4. Contractor's option to use truss or ladder
type.
B. Masonry Veneer Anchors: ASTM A 82.
1. Rectangular adjustable tie system with
wall eyelet sections welded to horizontal joint reinforcement 16
inches on center maximum.
2. Minimum wire size W2.8 (3/16 inch wire).
3. Hot dipped galvanized 1.5 oz. ASTM A 153, Class B2.
4. Provide wall tie pintle sections, at least
two, that fit into eyelet sections with maximum clearance of 1/16
inch.
5. Maximum offset for pintle anchors 1-1/4 inch.
6. Provide pintle anchors of sufficient
length to extend a distance at least ½ inch onto the outer face shell of
the masonry unit.
C. Deformed Bars: ASTM A 615, Grade 60.
1. Shop fabricate reinforcement shown as bent
or hooked.
2. Field
bending not allowed.
D. Anchor Bolts and Threaded Rods: ASTM A 307. Embed in masonry as shown in Structural
Drawings.
E. Bar Positioners for Vertical Wall Reinforcing Bars:
1. Minimum W.17 (9 gage) galvanized wire.
2.03. ACCESSORIES
A. Joint Filler: Closed cell foam, oversized 50 percent,
self-expanding.
B. Preformed Control Joint Filler
1. Materials:
a. ASTM D2000
rubber.
b. ASTM D 2287 PVC.
2. Provide 2-5/8 inch by 1-1/2 inch for regular
joint.
3. Provide 2-5/8 inch by 1 inch for tee
joint.
C. Preformed Expansion Joint Filler: [Reference to
appropriate ASTM specifications should be added per joint
filler manufacturers' recommendations: ASTM C 920,
ASTM D 994, or ASTM D 1056, Class 2A1].
1. One Inch Expansion Joint: Secondary
compression seal.
2. Materials
a. ASTM D 994 - Bituminous.
b. ASTM D 1056 - Cellular.
D. Through Wall Flashing:
1. Sheet copper combined with lead, total
weight 7 ounces per sq. ft., laminated with asphalt and bonded both
sides with creped surfaces and reinforced with
interspersing fiberglass strands.
E. Adhesive: As Recommended by flashing material
manufacturer.
F. Weeps: Galvanized steel or plastic tubes
2.04. MASONRY FILL INSULATION
A. Granular Insulation:
1. ASTM C 516 vermiculite.
2. ASTM C 549 perlite.
B. Foamed-In-Place: Subject to compliance with project
requirements and local jurisdictional restrictions,
manufacturers offering Foam-In-place Insulation tested
and found compatible and non-detrimental
within the indicated Underwriters Laboratory fire
resistance assemblies which may be incorporated
into the Work include:
1. Manufacturers:
2. Manufacturers - as approved by the architect.
PART 3 - EXECUTION
3.01. INSPECTION
A. Verification: Prior to the start of masonry construction
the Contractor shall verify:
1. Foundations are constructed with
tolerances conforming to ACI 117.
2. Reinforcing dowels are positioned in
accordance with Project Drawings.
3. Verify items provided by other Sections of
the Work are properly sized and located.
B. Notification: If conditions are not met notify the
Architect/Owners Representative.
3.02. PREPARATION
A. Establish Lines, Levels, and Coursing:
1. Protect lines from disturbance.
2. Use non-corrosive materials in contact
with masonry.
B. Surface Preparation: Prior to placing Quik-Brik remove
laitance, loose aggregate or other materials that would
prevent mortar from bonding to the foundation.
3.03. COURSING
A. Placement: Place Quik-Brik to lines and levels indicated.
B. Uniformity: Maintain masonry courses to uniform
width. Make vertical and horizontal
joints equal and of
uniform thickness.
C. Bond Patterns: Place Quik-Brik in ½ running bond
unless otherwise noted.
D. Course Height: Course one Quik-Brik and one mortar joint
equal to 4 inches.
3.04. PLACING AND BONDING
A. Bed and Head Joints:
1. Joint
Thickness:
a. Construct 3/8-inch bed and head
joints unless otherwise indicated.
b. Construct bed joint at starting
course on foundation not less than ¼ inch and not more than ¾
inch.
2. Fill holes not specified in exposed and below
grade masonry with mortar.
3. Tool head and bed joints concave unless
below grade or above ceiling height and to be concealed.
a. Use tool with large enough radius
that joint is not raked free of mortar.
4. Remove masonry protrusions extending
½ inch or more into cells or cavities to be grouted.
B. Unit Placement:
1. Quik-Brik: Lay units with bed and head
joints filled from the faces of the units to a distance in not less
than the thickness of the face shell.
a. Webs
are fully mortared in all courses of piers, columns, pilasters, starting course
on footings or
foundations, and where adjacent to cells or cavities to
be reinforced or filled with
concrete or grout.
b. Spread out full mortar bed, including
areas under cells, for starting course on footings where
cells are not to be grouted.
c. Vertical cells to be grouted are aligned
and unobstructed openings for grout are provided in
accordance with drawings.
2. Keep cavity airspace and weep holes clean
or mortar, clean out promptly if mortar falls into cavity airspace
or plugs weep holes.
3. In-Progress Cleaning:
a. Remove excess mortar.
b. Dry brush exposed masonry prior to
the end of each workday.
c. Protect wall from mud splatter and
mortar droppings.
i. Set scaffolds and scaffold boards so that
mortar is not deflected onto masonry.
ii. At end of each workday turn scaffold boards
so that rainwater is not deflected onto
masonry.
d. Place Quik-Brik such that mortar does not run down the face of the wall or smear the
masonry
face.
4. Adjustments:
a. Do not shift or tap Quik-Brik after
mortar has taken initial set.
b. Remove unit and mortar and
replace.
5. After joints are tooled, cut off mortar
tailings with trowel and dry brush excess mortar burrs and dust from
the face of the
masonry.
6. Fully bond external and internal corners
and properly anchor intersecting walls.
7. Termination of Wall Height:
a. For fire-rated walls, construct walls
to finish against bottom of roof or floor deck and fill voids
with firestopping.
b. For other than fire-rated walls, cut units
to match the slope of the roof deck and finish
construction to within 2-inches of an parallel to roof
deck.
8. Isolate masonry partitions from vertical
structural framing members with a control joint.
3.05. TOLERANCES: Erect masonry within the
following tolerances from specified dimensions:
A. Dimension of Elements:
1. In cross-section or elevation: -1/4 inch,
+ 1/2 inch.
2. Mortar joint thickness:
a. Bed:
plus or minus 1/8 inch or plus 1/8 inch.
b. Head: plus 3/8 inch or minus 1/4
inch.
c. Collar: plus 3/8 inch or minus 1/4
inch.
3. Grout space or cavity airspace except
where passing framed construction: plus 3/8 inch or minus 1/4 inch.
B. Elements:
1. Variation from level:
a. Bed joints: plus or minus1/4 inch in
10 feet; plus or minus 1/2 inch maximum.
b. Top of bearing walls: plus or
minus1/4 inch in 10 feet; plus or minus ½ inch maximum.
2. Variation from plumb: plus or minus 1/4
inch in 10 feet; plus or minus 3/8 inch in 20 feet; plus or minus
1/2 inch max.
3. True to line: plus or minus 1/4 inch in 10
feet; plus or minus 3/8 inch in 20 feet; plus or minus 1/2 inch
maximum.
4. Alignment of columns and walls (bottom
versus top):
a. Bearing: plus or minus 1/2 inch.
b. Non-bearing: plus or minus 3/4 inch.
C. Location of Elements:
1. Indicated
in plan: plus or minus 1/2 inch in 20 feet; plus or minus 3/4 inch maximum.
2. Indicated in elevation: plus or minus 1/4
inch in story height; plus or minus 3/4 inch maximum.
D. Notification: If the above conditions cannot be met due to
previous construction notify Architect/Owner's
Representative.
3.06. CUTTING AND FITTING
A. Coordination: Cut and fit for bearing plates, chases,
pipes, conduits, sleeves, and grounds. Coordinate with
other Sections of Work to provide correct size and
shape.
B. Notification: Prior to cutting and fitting any area not
indicated or where appearance or strength of masonry
work may be impaired, obtain approval from
Architect/Owner's Representative.
C. Cutting Method: Perform jobsite cutting with proper
tools to provide straight un-chipped edges and take care to
prevent breaking masonry unit corners or edges.
3.07. REINFORCEMENT AND ANCHORAGES
A. Basic Requirements:
1. Place reinforcement and anchorages in
accordance with the sizes, types, and locations indicated on the
Drawings, and
as specified.
2. Do not Place dissimilar metals in contact
with each other.
B. Details of Reinforcement:
1. Completely embed reinforcement in grout in
accordance with Article 3.08.
2. Maintain clear distance between
reinforcing bars and any face of masonry unit or formed surface:
a. Not less than 1/4 inch for fine
grout.
b. Not less than 1/2 inch for coarse
grout.
3. Splice only where indicated on Drawings,
unless otherwise specified.
4. Do not bend reinforcing bars after
embedded in grout.
5. Place vertical reinforcing bars supported
and secured against displacement by means of bar positioners.
6. Support bars other than vertical bars and
tie to prevent displacement.
7. Placement tolerances:
a. Tolerances for the placement of
reinforcing bars:
i. 1/2 inch when
the distance from the centerline of the reinforcing bar to the opposite
outside face of the masonry, d, is 8 inches or
less.
ii. 1 inch when the
distance from the centerline of the reinforcing bar to the opposite
outside face of the masonry, d, is 24 inches or less but more
than 8 inches.
iii. 1-1/4 inch when the distance from the
centerline of the reinforcing bar to the
opposite outside face of the masonry is more than 24
inches.
b. Place vertical reinforcing bars
within 2 inches of required location along the length of the wall.
c. If it is necessary to move bars more
than one bar diameter or a distance exceeding the
tolerances provided in
Section 3.06.C.7.a. to avoid
interference with other reinforcing bars, conduit, or embedded items,
notify the Architect/Owner's Representative for
the acceptance of the resulting
arrangement of bars.
C. Joint
Reinforcement:
1. Placement:
a. Install joint reinforcement at 16 inches on
center vertically, except space at 8 inches on center in
parapet walls and below finished floor unless
otherwise indicated on Drawings.
b. Place joint reinforcement continuous in
first bed joints below top of masonry wall and bed joint
8 inches below first bed joint below top of
wall.
c. Place joint reinforcement so that
longitudinal wire are embedded in mortar:
i. Minimum cover of 1/2 inch when not exposed
to weather.
ii. Minimum cover of 5/8 inch when exposed to
weather or earth.
d. Lap joint reinforcement ends minimum
6 inches.
e. Do not extend joint reinforcement
through control joints.
D. Wall Ties:
1. Embed ends of wall ties in mortar joints
at least 1/2 inch into outer face shell of hollow masonry
construction.
2. Unless otherwise required, install
adjustable wall ties in accordance with the following:
a. One tie for each 1.77 sq. ft. of wall area.
b. Do not exceed 16 in. on center
horizontally or vertically.
3. Install wire ties perpendicular to a
vertical line on the face of the wythe from which they
protrude.
4. Unless otherwise provided, install
additional unit ties around all openings larger than 16 inches in either
dimension. Space
ties around the opening at a maximum of 3 feet on center and place ties within
12
inches of the opening.
3.08. BUILT-IN AND EMBEDDED ITEMS AND
ACCESSORIES
A. Incorporation: As work progresses build in metal
doorframes, fabricated metal frames, window frames, anchor
bolts, diaphragm anchors, embedded plates, and
other items in the work supplied in other Sections.
B. Metal Door and Glazed Frames:
1. Embed anchors in mortar joints.
2. Fill frame void solid with grout.
3. Fill masonry cores with grout minimum 12
inches from framed openings.
C. Chases: Construct chases as masonry units are laid.
D. Pipes and Conduits: When required, place pipes and
conduits passing horizontally through masonry beams or
walls in steel sleeves or cored holes.
1. Place pipes and conduits passing
horizontally through non-load-bearing partitions piers, pilasters, or
columns.
2. When required, place horizontal pipes and
conduits in and parallel to the plane of the masonry wall.
E. Accessories: Install and secure connectors, flashing,
weep holes, nailing blocks, reglets and other accessories.
1. Install reglet level and parallel to
building lines. Set reglet as indicated
on Drawings to coordinate with
sloped roof surface.
F. Organic Materials: Do not build in organic materials
subject to deterioration.
3.09. GROUT PLACEMENT
A. Placement:
1. Place grout within 1-1/2 hours of
introducing mixing water and prior to initial set.
2. Prevent grout from flowing onto or
otherwise staining faces of CMU intended to be exposed.
B. Confinement: Confine grout to the areas indicated on the
Drawings.
C. Grout Pour Height: Use fine or coarse grout in accordance with requirements in
Section 04070.
D. Grout Lift Height: Place grout in lifts not to exceed 5
feet.
E. Consolidation: Consolidate grout at the time of placement.
1. Consolidate grout pours 12 inches or less
in height by mechanical vibration or puddling.
2. Consolidate grout pours exceeding 12
inches in height by mechanical vibration and reconsolidate by
mechanical vibration after initial water loss and
settlement has occurred.
3.10. BRACING
A. Design and Installation: Design, provide and install bracing
for walls, lintels, and other masonry work that will
assure stability of masonry during construction.
B. Duration: Maintain bracing in place until roof or other
structural elements are complete and provide permanent
support.
3.11. MASONRY FILL INSULATION
A. Install insulation in masonry unit cells of exterior
walls.
B. Granular Fill Insulation:
1. Verify that holes and openings have been
sealed to prevent escape of insulation.
2. Place masonry fill insulation in accordance with manufacturer's instructions.
3. Ensure spaces are free of mortar to allow
free flow of insulation.
4. Place as masonry is erected, completely
filling spaces. Place in lifts and rod
to eliminate air pockets.
Place prior to covering cores with bond
beams or lintels.
5. Place temporary signs on face of insulated
walls warning workers to use caution to prevent loss of
insulation if cutting into walls.
C. Foamed-In-place Insulation:
1. Confirm that selected foam insulation
material is compatible and non-detrimental to referenced fire
resistance assemblies before use.
2. Installer shall be certified and/or
approved by manufacturer of insulation. Install foam insulation in strict
accordance with manufacturer's published instructions.
3. Pump foam insulation bored into mortar
joints around entire wall area 3 feet from floor level. Repeat at
height no greater than 10 feet until completion of
wall area.
4. Plug holes with mortar after completion.
D. Blown-In Expanded Polystyrene Bead Insulation:
1. Verify that holes and openings have been
sealed to prevent escape of insulation.
2. Installer shall be certified or approved
by manufacturer of insulation.
3. Install expanded polystyrene beads in
accordance with manufacturer's published instructions.
4. Blow-in expanded polystyrene beads from
top of wall prior to installation of bond beams.
3.12. LINTELS
A. Steel Lintels:
1. Install loose steel lintels as scheduled.
2. Provide 9 gage Z-ties at each vertical
joint of soap units covering steel lintels. Weld Z-ties to web of steel
lintel.
B. Concrete Masonry Lintels:
1. Install reinforced unit masonry lintels
over openings where steel lintels are not scheduled.
2. Construct lintels using grout fill and
reinforcing.
a. Maintain minimum 8 inch bearing on
each side of opening unless otherwise noted on Drawings.
b. Use reinforcing bars of one-piece
lengths only.
c. Place and consolidate grout without
disturbing reinforcing.
3. Allow lintels to reach strength before
removing temporary supports.
3.13. MOVEMENT JOINTS
A. Control Joints:
1. Do not continue bond beams or joint
reinforcing across control joints.
2. Install preformed control joint filler at
locations indicated on Drawings.
3. Use proper size material to create sealant
joint space.
4. Backer rod and sealant installed in
accordance with Section 07900.
B. Expansion Joints:
1. Install expansion joint filler material on
centerline of wall at locations indicated on Drawings.
2. Backer rod and sealant installed in
accordance with section 07900.
C. Seismic Joints:
1. Provide seal and cover at both faces of
joint, as indicate don Drawings.
2. Secure seal to face of wall.
3. Provide un-faced batt insulation in cavity
between exterior and interior seal.
4. Provide fire barrier blanket in cavity
between exterior and interior seals of fire-rated separation wall.
3.14. CLEANING
A. In-Progress Cleaning: Clean unit
masonry as Work progresses by dry brushing to remove mortar fins and smears
before
tooling joints as described in Article 3.04.B.3.
B. Final Cleaning:
1. After mortar has set, reached initial
curing; within 7 days of completion of work for custom masonry units,
clean exposed masonry as follows:
2. Remove large mortar particles by hand with
wooden paddles and non-metallic scrape hoes or chisels.
3. Cut out any defective mortar joints and
holes and re-point with mortar.
4. Protect non-masonry surfaces from contact
with cleaning solution by covering them with liquid strippable
masking agent, polyethylene film, or waterproof
masking tape.
5. Clean Quik-Brik with proprietary masonry
cleaner.
a. Materials:
i. Custom Concrete Brick Cleaner, by Prosoco,
Kansas City
,
Missouri
(800) 255-4255, diluted one part cleaning
solution to at least three parts water.
b. Thoroughly wet surface of masonry.
c. Scrub using non-metallic brushes:
d. Immediately rinse with water.
e. Do small sections at a time.
f. Work from top to bottom.
6. Do not use high pressure cleaning methods.
a. Do not exceed nozzle pressure of 500
psi.
b. Use water flow of at least 4 gallons
per minute.
c. Use at least 40o fan nozzle.
d. Keep nozzle at least 18-inches from
face Quik-Brik.
7. Cleaned surfaces shall appear as
represented by mockup wall panel.
3.15. SEALING
1. Seal Quik-Brik with proprietayr masonry
cleaner
a. Materials
i. Customer Masonry Sealer, by
Prosoco
,
Kansas
City
,
Missouri
(800) 255-4255,
follow manufacturer's recommendations for applying
3.16. PROTECTIONS
A. External Corners: Maintain protective boards at exposed
external corners that may be damaged by construction
activities.
1. Provide protection without damaging work.
B. Base of Walls: Protect the base of walls from
rain-splashed mud and mortar droppings.
C.
Environmental:
At end of day, cover completed masonry to prevent moisture infiltration. Use the following
provisions unless
otherwise required for environmental conditions, Section 106:
D.
Load
Application:
1.
Do not
apply uniform floor or roof loading for at least 12 hours after building
masonry columns or walls
2.
Do not
apply concentrated loads for at least three days after building masonry columns
or walls
3.17.
FIELD
QUALITY CONTROL
A.
Masonry:
Required testing will be in accordance with Section 01450.
END OF SECTION
|